AN EXAMPLE OF APPLYING ALGORITHM TO CREATE THE APQ OF A HYDROGENERATOR-TURBINE UNIT
DOI:
https://doi.org/10.37798/2007564364Keywords:
end region, heating, hydrogenerator, operating tolerances, PQ diagram, synchronous generator, vibrationsAbstract
The work describes the application of the methodology of defining the actual PQ diagram (APQ) on the example of Hydrogenerator-turbine unit No. 3 at Vinodol HPP. Used as a basis for determining the unit’s operating tolerances was a block diagram which provides a clear survey of the sequence of steps required to create an APQ. All intermediate steps are documented and the obtained results are shown in tables and graphics. Each of finally defined limits is imported into the APQ of the observed unit. Considering the complexity of calculating the limit conditions imposed by electromagnetic and thermal occurrences in the end region, in a concrete example from practice the present work describes an entirely new methodology of determining the limit values of the longitudinal magnetic induction component, based on the results of measuring induction and pertaining over-temperature in the generator’s permanent capacitive operation.