Dielectric, Switching and System Requirements under Out-of-Phase Conditions, during Synchronisation and under Comparable Stresses

Authors

  • A.L.J. Janssen
  • F. Iliceto
  • Q. Bui-Van
  • S. Morais
  • M. Waldron
  • B. Middelton

DOI:

https://doi.org/10.37798/2010591-4286

Keywords:

Out-of-phase, synchronisation, TRV, RRRV, First-Pole-to-Clear Factor (fpcf), longitudinal dielectric stress

Abstract

Recent developments in electrical networks can increase the probability of out-of-phase switching and dielectric stresses being applied to open circuit-breakers, due to asynchronous systems at both sides. This report presents a systematic study of TRV-stresses associated with generator separation and system separation. TRV peak values are higher than required in the Standards, even for relatively small out-of-phase angles (75º to 90º), and the dielectric stresses are high with respect to the shortduration power frequency withstand voltages across a circuit-breaker open contacts, especially taking into consideration the external insulation under pollution and ageing processes. To the opinion of the authors, the Standards should be revised to give users clear and adequate guidance on the assessment and specification of TRV-values and dielectric withstand requirements under out-of-phase conditions.

Downloads

Download data is not yet available.

Published

2022-08-22

Issue

Section

Special Issue Article