The Abilities of TDSF and FDSF in Analysing Voltage Distribution in Different Types of Disc Windings of Power Transformers
DOI:
https://doi.org/10.37798/2026753781Keywords:
Transformers, lightning impulse, frequency domain severity factor, time domain severity factor, single turn modelAbstract
Power transformers are required to be engineered
to withstand overvoltages encountered throughout their operational
lifespan. Typically, transformers are specified and assessed
according to standard impulse waveshapes, such as the
lightning impulse (1.2/50 μs), chopped lightning impulse, and
switching impulse (250/2500 μs). Nonetheless, actual overvoltages
within the power system may deviate from these standard test
impulses. Consequently, it is essential to assess the severity of
measured overvoltage waveshapes from the power system and
their potential impact on transformer insulation. In the literature
three established approaches for waveshape comparison exist:
frequency domain severity factor (FDSF), time domain severity
factor (TDSF), and the technique outlined in IEC 60071-2:
2023, Annex I. This study examines the effect of non-standard
overvoltages on transformer insulation by employing two severity
assessment methodologies: the Frequency Domain Severity Factor
(FDSF) and the Time Domain Severity Factor (TDSF). Nonstandard
waveshapes are generated through systematic variation
of parameters - such as front time, tail time, chopping time, fall
time and undershoot - based on those defined in IEC 60076-
3: 2018. This controlled methodology facilitates the isolation of
individual waveform parameter influences on internal transient
responses. The study applies these waveforms to detailed whitebox
single turn models of multiple transformer windings with disc
ordinary, partially interleaved, fully interleaved and disc shielded
arrangements. With the voltage distribution within the windings
the severity of the generated non-standard waveforms is assessed
in relation to the standard impulses. Consequently, the validity of
the standard-defined waveforms for testing transformer winding
insulation is evaluated. The results show that FDSF effectively
highlights changes in spectral excitation introduced by fast
fronts, short fall times, and large undershoots, whereas TDSF
more directly captures localized dielectric stress along critical
insulation paths within the winding. The study demonstrates
that relying on a single severity metric can be misleading and
that a combined FDSF and TDSF assessment provides a more
robust basis for judging the insulation relevance of non-standard
overvoltage waveforms.