Geomagnetically induced currents and influence on power transformer saturation

Authors

  • Antonio Gloc Končar Distribution and Special Transformers
  • Bruno Jurišić
  • Božidar Filipović-Grčić

DOI:

https://doi.org/10.37798/2026753768

Keywords:

EMTP, Geomagnetic electric field, Geomagnetic storms, Geomagnetically induced current

Abstract

The paper studies geomagnetic disturbances and their impact on the electric power system. The resulting geomagnetically induced currents (GIC) have a very low frequency, in the range of 0.01 Hz to 0.5 Hz, and can therefore be considered quasi-direct current. The entry of direct current into a transformer can lead to its saturation, resulting in excessive heating, a significant increase in reactive power consumption, and the generation of even and odd harmonics. Increased reactive power consumption lowers the voltage in the network, while the produced harmonics interfere with the operation or can trigger unintended activation of relay protection systems or disconnection of reactive power compensators. Simulations were conducted using the EMTP software, in which a model of the IEEE 118-bus test system was developed. The impact of geomagnetic electric fields (GEF) of varying intensities and different angles of incidence relative to transmission lines was analyzed. The transformer connection group, protective measures, key results, and conclusions regarding the simulation of nonlinear and frequency-dependent models are also presented.

Downloads

Download data is not yet available.

Downloads

Published

2026-11-20