Geomagnetically induced currents and influence on power transformer saturation
DOI:
https://doi.org/10.37798/2026753768Keywords:
EMTP, Geomagnetic electric field, Geomagnetic storms, Geomagnetically induced currentAbstract
The paper studies geomagnetic disturbances and their impact on the electric power system. The resulting geomagnetically induced currents (GIC) have a very low frequency, in the range of 0.01 Hz to 0.5 Hz, and can therefore be considered quasi-direct current. The entry of direct current into a transformer can lead to its saturation, resulting in excessive heating, a significant increase in reactive power consumption, and the generation of even and odd harmonics. Increased reactive power consumption lowers the voltage in the network, while the produced harmonics interfere with the operation or can trigger unintended activation of relay protection systems or disconnection of reactive power compensators. Simulations were conducted using the EMTP software, in which a model of the IEEE 118-bus test system was developed. The impact of geomagnetic electric fields (GEF) of varying intensities and different angles of incidence relative to transmission lines was analyzed. The transformer connection group, protective measures, key results, and conclusions regarding the simulation of nonlinear and frequency-dependent models are also presented.
Downloads
Downloads
Published
Issue
Section
License
Copyright (c) 2026 Journal of Energy - Energija

This work is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License.