Design of transformers for very fast transient overvoltages

Authors

  • Álvaro Portillo Ing. Álvaro Portillo - Transformer Consultant

DOI:

https://doi.org/10.37798/2026753753

Abstract

Increasingly, for different technical-economic reasons, gas-insulated substations (GIS) are being used in electrical systems instead of conventional air-insulated substations (AIS). The switching transients originating in GIS are called Very Fast Transient Overvoltages (VFTO) and are completely different from those originating in AIS, with different frequencies, amplitudes and waveforms. Conventional power transformers are designed to withstand the standard lightning and switching impulses (LI, LIC and SI according to IEC 60076-3). Modelling and behaviour of transformers for the frequency range of these tests (< 500 kHz) is well known, proved in the factory acceptance tests, and validated by successful operation in service. For VFTO, , however, no standard tests are available yet, therefore, the customer needs to define the VFTO test voltage that must be considered in the design of the transformer. The design of transformers that can withstand the effects of VFTO represents a great challenge and we will present in this work the state of the art of the dielectric design methodology including the selection of voltage wave shapes representative of VFTO, the transformer modelling requirements, the admissible electric field in insulating materials, the withstand of the different insulating structures and finally the proposed non-standard tests, when a transformer will be subjected to the effects of VFTO.